Laserfiche WebLink
<br /> I' <br /> ~e <br /> I TABLE #1 <br /> I SAFE MAX MAXIMUM <br /> I OPERATING ALLOWABLE ACCURACY % @ :I: 1.5% <br /> SIZE CAPACITY PRESSURE LOSS MINFLOWRATE TEST FLOW <br /> I 5/S" x 3/4" 25 GPM 5 PSI/20 GPM 95% @ 1/4 GPM 1/2-25 GPM <br /> 3/4" 35 GPM S PSI / 30 GPM 95% @ 3/S GPM 3/4-35 GPM <br /> I I" 70 GPM 7PSI/ 50 GPM 95% @ 3/4 GPM 1-1/4 -70 GPM <br /> 1-1/2" 120 GPM 7 PSI! 100 GPM 95%@ 1-1/4 GPM 2-1/2 -120 GPM <br /> I <br /> 2" 170 GPM 7 PSI / 160 GPM 95%@ 1-1/2 GPM 2-1/2-170 GPM <br /> I <br /> Ie <br /> I 1.13 DISC NUTA TIONS/OSCILLA TIONS: Because the City of Arden Hills expects the <br /> proposed meters to have a long service life, disc nutations shall not exceed the amounts <br /> shown in Table #2. <br /> I <br /> 1 TABLE #2 <br /> I MAXIMUM <br /> SIZE <br /> NUT ATIONS /OSCILLA TIONS <br /> I <br /> 5/S" x 3/4" 50/ GALLON <br /> I 3/4" 32/GALLON <br /> I" 12/ GALLON <br /> I 1-1/2" 6/ GALLON <br /> ,. 2" 4/ GALLON <br /> I 3 <br />