Laserfiche WebLink
<br />City of Arden Hills, MN – 25X.137753 LIFT STATION CONTROL SYSTEM <br />January 2026 PAGE 26 90 04-9 <br />©2026 Design Tree Engineering, Inc All Rights Reserved <br />b. The level control mentioned below shall be as sensed by the level transducer. <br />c. When the wet well level is below the PUMP START elevation, the pump shall be off. <br />d. When the wet well level rises above the PUMP START elevation for a preset time, the pump <br />shall start. The VFD shall then modulate to the adjustable PUMP MINIMUM SPEED setpoint. <br />e. If the wet well level stays at the PUMP START elevation or starts to drop, the pump shall stay at <br />the minimum pumping speed. If the level rises, the pump’s speed shall be increased until the <br />maximum speed setpoint is reached. <br />f. If the wet well level starts to drop, the pump shall decelerate until it eventually reaches the <br />PUMP MINIMUM SPEED. If the level drops below the PUMP STOP elevation for an adjustable <br />time, the pump shall be stopped. <br />4. A restart delay relay shall prevent the pump from starting for an adjustable time delay of 0 to 3 <br />minutes after it has stopped. The RESTART DELAY indicator shall be displayed on the operator <br />interface screen during the restart delay period. <br />a. The restart delay timer setpoints shall be operator adjustable via the operator interface. <br />F. Process engineer will provide programmer with initial VFD ramp times and operating speeds. <br />G. When a VFD is required to operate while under PLC control, PLC shall produce a digital required signal <br />to the VFD and a 4-20mA analog signal generated by the PLC for use of VFD speed control. The analog <br />signal shall be proportional to the desired speed. <br />H. If when in AUTO and the process level drops below the “Low Water Alarm” level setpoint, the system <br />shall shut down the pump and signal a LOW LEVEL ALARM after an operator entered time delay. <br />I. If when in AUTO and the process level activates the “High Water Alarm” level setpoint, the system shall <br />signal a HIGH WATER LEVEL ALARM after an operator entered time delay. <br />J. Two float backup control mode (While in control mode selector switch is AUTO position): <br />1. Backup control shall be provided by 2 floats. Control relays and timers is to be provided for the <br />backup control and shall be independent of the transducer and PLC controller. <br />2. High Level Float: If the wetwell level rises to an elevation which activates the High-Level Float for an <br />adjustable amount of time, the control system shall go into a Backup Control Mode. The High-Level <br />Alarm float shall initiate a High Wetwell Alarm which shall be signaled over the SCADA system, and <br />start the pump. <br />3. Low Level Float: If the wetwell level drops below the Low-Level Float the control system shall <br />discontinue the required signal to the operating pump and the control system and shall go into the <br />Backup Control Mode if not already in this mode. <br />4. When backup control mode is active, an alarm shall be indicated on the SCADA system screens. <br />Operator may transfer control back to PLC control by utilizing a simulated pushbutton on the OIT <br />screen. <br />5. The backup start signal shall be connected to a preset speed input of each VFD. Speed setpoint <br />shall be coordinated with the process engineer at time of startup. <br />6. When in float backup mode, the control system shall not signal a high- or low-level alarm when the <br />floats are activated. The low- and high-level alarms shall be signaled when the system is under PLC <br />and transducer control. <br />a. The exception to this, is if the high wetwell float remains activated for a preset amount of time <br />after pump is called to operate while backup mode is activated, the control system shall signal <br />a backup mode high level alarm.