Laserfiche WebLink
<br />J. <br />1. <br />] <br />J <br />] <br />] <br />] <br />] <br />] <br />]. <br />] <br />J <br />] <br />J <br />] <br />U <br />U <br />. <br />U <br />~J <br /> <br />Zone or Room Identification <br /> <br />VAV-11 Room #201 <br /> <br />Test Spec. Mode Test Procedure Expected Pass Fail Notes <br />10 Section Response <br /> 15950 <br />1 Based on Occupied Unit commanded to occupied Verify by visual <br /> NA.C. mode. inspection that zone is <br /> drawings listed as occupied on X Note 1 <br /> cOmputer <br /> Occupied set points Verify that all occupied <br /> set points are enabled X <br /> Air damper modulation Air damper modulates to <br /> control to required X Note 5 <br /> C.F.M. <br />2 Radiation control Verify radiation valve X Note 4 <br /> opens on a call for heat <br />3 3.o3C Off Reheat control Verify reheat valve is <br /> opened on a can for X <br /> . heat. <br />4 3.l14B Winter Review ....ogramming Verify controller has <br /> ISummer been programmed ..... <br /> Winter/summer change X Note 3 <br /> over. <br /> <br />Notes: 1. Occupiedlunoccupied point not brought out on computer lor anyVAV boxes. <br />2. Box is unable to produce maximum C.F .M. requirements. Max. C.F.M. required is 690. box only puis out 460 C.F.M. <br />3. V.MA conIroIter is not programmed lor dual minimum box. <br />4. V.MA controller was locked up. R~ controller and radiation valve is oow worldng. <br />5. Box unable 10 produce maximum C.F.M. requirements. Max C.F.M. required is 3000. box only puis out ll00c.F.M. <br />6. Radiation.- was _. Corrected rotation lor Pfoper __no <br />7. V.MA flow station reads 0 C.F.M. cOlltinuously. Troulileshotlling will be required. <br />8. V.M.A damper actuator will not move. Controller needs to be replaced. <br />9. Static pressure control should be tuned for better control. <br /> <br />File: FPVAV_FinaIReport.doc <br /> <br />Page 3 of 5 <br />