Laserfiche WebLink
PART 2PRODUCTS <br />2.01 FIRE ALARM CONTROL PANELS <br />A. Control panel operator convenience features: <br />1. Wide viewing angle 2 x 20 (40 character) alphanumeric LCD and dedicated LEDs <br />provide convenient panel status information. <br />2. Operation is programmable using a multi-function keypad and the panel LCD or via <br />service computer (PC) <br />3. RS-232 service port provides upload/download PC access for panel configuration and <br />event history logs <br />4. Software updates are via PC download <br />5. Convenient library of standard custom label terms <br />6. Standard on-board DACT provides: Contact ID, 3/1, 4/2, BFSK, and SIA formats <br />7. WALKTEST silent or audible system test <br />8. Voltage and current for both the battery charger and the battery can be displayed at <br />the front panel LCD <br />B. Five Initiating Device Circuits (IDCs): <br />1. Five Class B IDCs with optional expansion to ten, all with individual zone disable <br />2. Monitor 2-wire or 4-wire initiating devices including TrueAlarm smoke detectors <br />3. Optional Class A Adapter Module <br />C. Two Notification Appliance Circuits (NACs): <br />1. Class A or Class B outputs with solid state overcurrent protection per NAC, each rated <br />for 2 A <br />2. Selectable for Simplex® SmartSync two-wire horn/strobe control or synchronized strobe <br />control <br />D. Power Supply: <br />1. Provides 3 A maximum @ nominal 24 DC <br />2. Automatic input power selection operates with 120 VAC or 240 VAC, 50 or 60 Hz <br />3. On-board temperature compensated battery charger for up to 12.7 Ah batteries in <br />cabinet (UL and ULC). <br />E. Features: <br />1. Programmable Active Status Reminder <br />2. Two auxiliary relays <br />3. IDCs, NACs, and Relay outputs are power limited (AC input, battery circuits, and City <br />Circuit Module outputs are non-power limited) <br />4. Available with beige or red cabinet <br />5. UL listed to Standard 864 <br />6. 3 A Expansion Power Supply with two on-board 2 A NACs that operate the same as <br />standard NACs as required for devices served. <br />7. Expansion IDC module with five Class B IDCs as required for devices served. <br />8. Class A IDC Adapter Module, City Interface Module, and Auxiliary Relay Module as <br />required for devices served. <br />F. Manufacturer: Simplex Grinnell 4006 or equal. <br /> ALARM AND DETECTION SYSTEMS <br />© 2020 Stantec | 193805054 28 31 00 - 2 <br /> <br />