Laserfiche WebLink
Hydrant Locations Around Building and Parking Lot <br />• 10 Hydrants total per plans? <br />Response: <br />10 hydrants are being proposed on the site. <br />• Flow requirements to abide by MSFC Table 507.3 and NFPA 13 <br />Response: <br />Acknowledged. <br />Building Doors Labeled <br />• Due to the size of the industrial building, the Centennial Fire District is requesting that all exterior <br />doors to be labeled or numbered for ease of identification <br />o Example: Door 1, Door 2, etc. <br />Response: <br />Exterior doors will have exterior vinyl numbers. <br />Rack Storage <br />• Rack storage is to comply with NFPA standards for storage <br />Response: <br />Acknowledged. <br />Fire Lanes and Turning Radius <br />• Fire Lanes shall be established at all main entrances and coordinated with the Fire Marshal <br />Response: <br />Acknowledged. <br />• Turning radius shall be a minimum of 45ft to accommodate Centennial Fire District apparatuses <br />on cul-de-sacs and parking lots <br />Response: <br />Acknowledged. <br />• What is the "Rescue Vehicle Area" going to be utilized for on page C304? <br />Response: <br />The "rescue vehicle area" has been revised to "van problem solve spaces" on Site Plan <br />sheet C304. The area is intended to be used for temporary parking of tenant vans for <br />service/inspection. <br />Ryan Companies US, Inc. <br />533 South Third Street, Suite 100 <br />Minneapolis, Minnesota 55415 <br />ph:612-492-4000 <br />ryancompanies.com <br />