Laserfiche WebLink
<br />907.2.11.22 System response. The activation of two or more smoke <br />detectors, a single smoke detector with alarm verification, the alitomatic <br />sprinkler system or other approved fire detection device shall automaticlly: <br />1. Cause illumination of the means of egress with light of not less than 1 <br />foot-candle (11 Lux) at the walking surface level; <br />2. Stop any conflicting or confusing sounds and visual distractions; and <br />3. Activate an approved directional exit marking that will become <br />apparent in a emergency. <br /> <br />Such system response shall also include activation of a prerecorded <br />message, clearly audible throughout the special amusement building, <br />instructing patrons to proceed to the nearest exit. Alarm signals used in <br />conjunction with the prerecorded message shall produce a sound which is <br />distinctive from other sounds used during normal operation. <br /> <br />The wiring of the auxiliary devices and equipment used to accomplish <br />the above fIfe safety functions shall be monitored for integrity in <br />accordance with NFP A 72. <br /> <br />907.2.11.3 Emergency voice/alarm communication system. An <br />emergency voice/alarm communication system, which is allowed to serve as <br />a public address system. Shall be installed in accordance with NFP A 72 and <br />be audible throughout the entire special amusement building. <br /> <br />SUPPRESSION <br />903.2.15 Other required suppression systems. In addition to the <br />requirements of Section 903.2, the provisions indicated in Table 903.2.15 <br />also require the installation of a suppression system for certain buildings and <br />areas. <br /> <br />Table 903.2.15 <br />Section : International Building Code: Sprinkler requirements as set forth <br />in Section 903.2.15 of the International Building Code. <br /> <br />SUPPRESSION and ALARMS <br /> <br />2000 International Building Code <br /> <br />903.2.15 Other required suppression systems. In addition to the <br />requirements of Section 903.2, the provisions indicated in Tanble 903.2.15 <br />also requires the installation of a suppression system for certain buildings <br />and areas. <br />