Program (NURP). <br />5. Provide for overflow routes to drain low points along streets or lot lines to ensure a <br />freeboard of 2' from the lowest exposed structure elevation and the calculated 100 - <br />year storm HWL elevation. Design criteria verifying the adequacy of the overland <br />drainage route capacity is required. At low points in the street, the catch basin grates <br />shall be assumed to be 50% plugged for design purposes. <br />6. The storm sewer alignment shall follow the sanitary sewer and watermain alignment <br />where practical with a minimum of 10' of separation. Storm sewer placed along the <br />curb alignment shall be along the curb opposite the watermain to maintain the 10' <br />separation. <br />Catch basins shall be located on the tangent section of the curb at a point 3' from the <br />radius. Mid -radius catch basins will not be allowed. Also, catch basins shall be <br />designed to collect drainage from the upstream side of the intersection. <br />8. The maximum spacing between manholes is 400'. <br />9. Manholes steps will be aligned and over the downstream side of the manhole. Steps <br />within manholes will be: <br />V+ horizontal alignment <br />1 "+ vertical alignment with 16" spacing as the standard <br />10. Any connections to existing manholes or catch basins shall be core drilled or the <br />opening cutout with a concrete saw. No jack hammering or breaking the structures <br />with a maul is permitted. Also, all connections to an existing system will require a <br />manhole for access. <br />11. To the greatest extent possible, manholes shall be placed in paved surfaces outside of <br />wheel paths (3' and 9' off centerline) or other readily accessible areas. <br />12. Minimum pipe size shall be 12" in diameter. <br />13. Type of pipe shall be Reinforced Concrete Pipe (RCP). All storm sewer pipe beneath <br />roadways or pavement shall be Class 5. The table below shows the allowable class of <br />pipe for storm sewer outside of the roadway: <br />PIPE DIAM. CLASS 2 CLASS 3 CLASS 4 CLASS 5 <br />12" — 18" X <br />21" X X <br />2411-3311 X X X <br />> 36" X X X X <br />Show the class of pipe in the profile view only. For areas outside of the roadway, the <br />City may allow the use of HDPE (High Density Polyethylene) pipe. <br />