Laserfiche WebLink
ATTACHMENT 1 <br />31.Storage 16 - Dry Sprinkler System Access room - Improper firestop of wires from <br />electrical box. Observed unpermitted alterations to electrical system. <br />32.Storage room 111 – <br />a.No path of egress. <br />b.Missing escutcheon on sprinkler heads. <br />33.Improper firestop of penetration in fire-rated ceiling in elevator equipment room. <br />34.Wires from electrical panels penetrate fire-rated ceiling without fire stop. <br />35.Washing machine pump controls are hanging by wires. <br />36.Stair towers throughout building have holes in fire-rated assemblies and appear to have <br />unrated electrical boxes installed in fire-rated walls. <br />37.Exit door in South stairwell does not close or latch. <br />nd <br />38.2 floor common area laundry has broken escutcheon on sprinkler head. <br />rd <br />39.3 floor employee room – <br />a.Improper firestop of penetration in fire-rated ceiling. <br />b.Cooking appliance has been installed, no hood/exhaust provided. Electrical <br />connection completed without permit. <br />c.Walls and stove are grease laden. <br />d.Windows are inoperable. <br />e.Fire extinguisher expired, not mounted. <br />40.Improper plumbing connections on all ice machines. <br />41.Roseville Room: <br />a.Sink trap penetrates fire-rated wall without a proper firestop. <br />b.Extension cords used as permanent wiring. <br />Qbhf!3:!pg!558 <br /> <br />