Laserfiche WebLink
<br />25 <br /> <br />6-220 All pilot burners shall be supported in such a. manner that their posi- <br />tion relative to the main burner or burners will remain fixed. <br /> <br />6-221 Pilot lines shall be connected to vertical supply lilles when possible. <br />When horizontal line is used, connection must be made on top or side. <br />Connection must be ahead of all controls including regulator and <br />appliaace shut-off and shall be provided with a separate shut-off <br />cock. 'Where gas pressure is greater than that for which pilots are <br />designed a pressure regulator (pilot regulator) must be installed on <br />the downstream side of pilot line shut-off cock. <br /> <br />6-222 A shut-off cock must be installed on branch line to safety pilot and <br />to each branch line to plain pilot system. <br /> <br />6-223 A manually operated approved shut-off cock shall be installed adjacent <br />to the gas burner on the down stream of all other control valves either <br />manual or automatic. Such cock shall be so located that it is readily <br />accessible and shall clearly indicate the lion" and "off" position, or <br />direction of rotation to open or close. This valve or cock must have <br />hamtle securely attached in such a manner that it may not be readily <br />removed. When gas pressures are greater than 1 psig the cock must be <br />of the lubricated plug type. Gate or gloVe type valve will not be <br />acceptable. Provide bIecidel'! line or other approved method of insuring <br />against gas leakage to boiler during shur down periods. <br /> <br />6-224 A manually operated approved type lubricated shu:b-off cock shall be <br />installed at each boiler or furnace ahead. of all control valves aDd <br />regulators except pilot line. This cock shall be so located that it is <br />readily accessible and shall clearly indicate the on or off position or <br />direction of rotation to open and close. Cock shall be provided with a <br />suitable operating handle permaneitly attached. Gate or globe valve <br />will not be acceptable.. <br /> <br />6-225 Electric control valves shall be installed according to the instructions <br />furnished by the manufacturer. <br /> <br />6-226 All electrical connections shall be made in conformity with the provis- <br />ions of. all codell relating to the installation of electric wiring wi thin <br />the municipality. <br /> <br />6-227 A gas pressure regulator approved by the Heating Inspector shall be <br />installed on all gas burner installations. <br /> <br />6-228 Each boiler or fumace shall be equipped with safety devices to limit <br />high steam pressures or watjr temperatures, low-water level and high <br />air temperatures. Where boiler or furnace is equipped with so-called <br />power burner, where air for combustion is furnished by means other than <br />a natural draft stack or where boiler b111"llers are so sized and designed <br />to require forced or induced draft or both, the gas and air supply shall <br />be equipped' with suitable controls to prevent functioning of the gas <br />supply until air supply is adequate for proper combustion, or in the event <br />of failure of air supply to shut off the gas supply. <br /> <br />6-229 Where forced draft equipment is used, a manual cutout control switch may <br />be installed subdect to approval, to eemit lighting off the burner under <br />natural draft, normal opera'tion under forced draft to remain under safety <br />control. <br /> <br />-50- <br />