<br />. . <br />.. Page 7 <br /> City of Arden Hills, Minnesota <br />. AEC Project No. MN 1410 <br />. and exterior of the wet riser) are in only fair <br /> condition and are not repairable. The coating <br />. in this area should be replaced concurrently <br /> with the interior wet. <br />II 2.3.3 After structural repairs completed, the <br /> are <br />. appropriate areas should be spot or completely <br /> abrasive blasted and the coating repaired with a <br />. compatible alkyd coating and replaced with an <br /> epoxy coating similar to Tnemec Series 66. <br />. 2.4 Exterior structural <br />. 2.4.1 Replace the tank vent/finial with a 24-inch <br /> diameter, removable top, mushroom vent, similar <br />. to the one shown on AEC drawing 6. See <br /> photo 26. The new vent and vent screen design <br />. should meet AWWA 0100 .and local Health <br /> Department Regulations. The removable top will <br />. improve ventilation and provide access to the <br /> tank interior during reconditioning. <br />. 2.4.2 Install two (2) , 24-inch diameter, hinged roof <br />. manways, approximately 180 degrees apart and <br /> located within 3 feet of the roof edge. This <br /> will provide conformance with OSHA Confined <br />. Space Entry Requirements and additional <br /> ventilation during the interior surface <br />. preparation and coating. See AEC drawing 7. <br />.. <br />. <br />