Laserfiche WebLink
<br /> . <br /> b. Recommendation <br /> The south tank pressure sensor should be moved away from the booster pumps to <br /> . an existing pit at base of south tower where effects of booster pumps would be <br /> minimized. This is the normal area of placement on water towers. Much of this <br />- work could be done by staff. <br /> c. Problem 2 Costs <br /> Staff has received quotes from three (3) electrical contractors on moving the south <br /> tank pressure sensor. The electric portion of this project would be by AID <br /> Electric of Fridley, Minnesota and it would be cost plus not to exceed $1,536.00. <br /> 3. Problem 3. <br /> The electric motors which run the north tower booster pumps were made in the 1960's <br /> era. These motors are not very efficient. <br /> a. Consequences <br /> The NSP rates are adjusted as to the efficiency of the motors, Therefore, we pay a <br /> higher user rate. Reviewing our electric bills over a one (l) year period we found <br /> we have been penalized over $600.00 this past year. <br /> b. Recommendation <br />- A power factor corrector should be installed on our electric motors. This would <br />- make our motors more efficient and lower rates even more. Expected payback on <br /> . this would be two (2) to three (3) years. <br />- <br /> c. Problem 3 Costs <br /> Staff also received quotes from three (3) electrical contractors on the installation <br />- of two (2) 9K V AR Capacitors, Aid Electric has the best bid on this work also at a <br /> cost plus basis not to exceed $1,711.00. <br />- <br /> En~ineerinl:": <br /> Staff has not yet reviewed these recommendations with the City Engineer. <br />- <br /> Recommendation: <br /> Staff recommends tllat the Council direct staff to work with the City Engineer on these proposed <br />- modifications and upon completion of this review prepare formal action by the City Council at a <br /> future meeting. <br />.- <br />- <br />- <br />- <br />- <br />- . <br />- <br />- <br />- <br /> - .. <br />