Laserfiche WebLink
<br />J. <br />]. <br />1 <br />] <br />] <br />] <br />J <br />U <br />U <br />o. <br />o <br />o <br />o <br /> <br />o <br />o <br />o <br />0. <br />u <br />u <br /> <br />Zone or Room Identification VAV-2 Room101/102 <br /> <br />Test Spec. Mode Test Procedure Exp&cted Pass Fail Notes <br />IV Section Response <br /> 15950 . . <br />1 Based on Occupied Unit commanded to occupied Verily by visual <br /> NAC. mode. inspection that zone is X Note 1 <br /> drawings listed as occupied on <br /> compu\ef <br /> Occupied set points VerifY that all occupied <br /> set points are enabled. X <br /> Air damper modulation Air damper modulates to . <br /> cont.rol to required X Note 8 <br /> . ' c.F.M. ... <br />2 . Radiation control Verily radiation valve X . Note 4 <br /> .. opens on a call for heat <br /> . <br />3 3.03C 011 Reheat control Verily reheat 1IlIIveis <br /> opened on a ""II tor X <br /> heaL <br />4 3.l14B Winter Reviewprograrnning Verily controller has <br /> /Summer been progranvned tor . Note 3 <br /> winter/summer change .. X <br /> ! over~ <br /> <br />End Of Test <br /> <br />Notes: 1. Occupied/tJnoccupied pointnotbroughl out on computer lor anyVAV boxes. <br />2. Box is unable to produce maximum C.F.M. requirements. Max. C.F.M. required is 690, box only puts out 460 C.F.M. <br />3. V.M.A. controller is not programmed for dual minimum box. <br />4. V.M.A. controUer was locked up. Re-d\>Wn1oaded controller .and raa_ valve is now worIdng. <br />5. Box unable to produce maximum C.F .M. requirements. Max C.F.M. required is 3000, box only puts oulll00c.F .M. <br />6. Radatioo rotation was backwards. Corrected rotation lor proper operation. <br />7. V.M.A. flow station reads 0 C.F .M. continuously. Troubleshootln9 will be required. <br />8. V,M.A damper actuator wit not move. C0ntr0lIer needs to be replaced. <br />9. Static pressure control should be tuned for -. control. <br /> <br />File: FPVAV_FinaIReport.doc Page 5 of 5 <br />