My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
CCP 03-31-2003
ArdenHills
>
Administration
>
City Council
>
City Council Packets
>
2000-2009
>
2003
>
CCP 03-31-2003
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
5/8/2007 1:18:18 PM
Creation date
11/14/2006 2:34:55 PM
Metadata
Fields
Template:
General (2)
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
279
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
<br />L <br />~~~. <br />8~'''~~J~ <br />i <br />I <br />1 <br />I <br />I <br />I <br />1 <br />I <br />1 <br />J <br />I <br />I <br />,J <br />1 <br />I <br />,I <br />I <br /> <br />Functional Test <br /> <br />. <br /> <br />Project: Arden Hills City Hall <br /> <br />Equipment Tag: AHU-2 & Audiovisual Room <br /> <br />Party filling out this form & witnessing Grea Zernechel <br /> <br />Date of test: 30 Jan 03 <br /> <br />Air Handler 2: <br /> <br />Air handler 2 is a single zone unit providing tempered air to the city council chambers <br />and associated areas. . This unit re~.ets its discharge air temperature betWeen 550 and 950 <br />based on the zone temperature set point that can be adjusted at the local thermostat. <br />This unit is not operating according to the original design specifications as described in <br />section 3.09 in control section 15950. Furthennore, the current operation ofthe unit does not <br />match the sequence of operation as described in the as built drawings delivered to the owner <br />from the controls contractor. <br />ThislJnit has a control-wiring problem that could potentially damage the equipment and <br />should be corrected as soon as possible. Refer to the functional test results for this unit and <br />the low temperature protection device section. <br />Please see this section for further infonnation on all observations. <br /> <br />. <br /> <br />Audiovisual Room: <br /> <br />This is the control room with all of the equipment needed to broadcast from the city <br />council chamber. The owner reports that the room overheats and creates an uncomfortable <br />work environment. The original drawings state that the room should receive 150 C.F.M. of air <br />from air handler 2, but this amount is not enough air to provide adequate cooling. <br />Additionally, if the main council chamber is callJng for heat, this area's temperature control <br />problem is only increased. <br /> <br />This area could be better served if a small, self-contained cooling unit was added to <br />offset the heat load of this space. <br /> <br />. <br />
The URL can be used to link to this page
Your browser does not support the video tag.