<br />n <br /> <br />n <br /> <br />n <br /> <br />o <br /> <br />o <br /> <br />o <br />o <br /> <br />o <br /> <br />o <br /> <br />o <br />o <br />o <br /> <br />o <br /> <br />o <br /> <br />o <br /> <br />o <br />o <br /> <br />u <br />o <br /> <br />Test Spec. Mode Test Procedure Expected Pass Fail Notes <br />10 Section Response <br /> 15950 <br />7 3.10J SF Static HI Simulate static pressure 1" higher SF & RF shut down. X NoIe 10 <br /> Umit than set point. <br /> OA & RE dampers close. X Note 10 <br /> Alann to BAS X Note 10 <br />8 3.10K Filter Alarm Simulate high differential Verily lhal BAS reports X NoIe 11 <br /> pressure across filters. an alann. <br />9 3.10G Firelsmoke Sltnulalellrelsmoke condition. NOT Tested. <br /> <br />. <br /> <br />End Of Test <br /> <br />. <br /> <br />Notes:" Testing of AHU #3 was performed using HVACPro. <br />1. MaIn compu1er is not setup for alarms. U.N.T. controller is not programmed properly, pressure wiD always read O. <br />2. Unable to1est because of outside air temperature. <br />3. Supply fan status does not work. S1atus continually shows on. <br />4. Intine fan 5, (IF-5) has no points on controIer. Fan is only conlrolled by Ioc;al switch in rnech. room. <br />5. Fan stalus is not wired to proper point on c_oner. <br />6. CootroUer is not programmed for warm up mode. <br />7. Economizer mode is locked out on outside air lemperaiure set point. <br />8. OX cooling is never locked out. ~ide air temperature is not being written 10 controller and set point for lockout is at 20". <br />9. Low IimU protection device is wired 10 the supply fan status point No alarm is generated. <br />10. Opening con1acIs dIdn, shut down unit. No alarm is generated. <br />1 f. Main computer is not setup for alarms. U.N. T. controller is nol programmed properly. pressure wiR always read OHler slatus is <br />not on computer. <br />12 No motorized rerlel damper insIalled. <br />13. Radiatioo wive is conIroDed by separate zone set poinl nollrom slider on thermostat <br /> <br />. <br /> <br />File: AHU3_FinaIReport.doc <br /> <br />Page 6 of 6 <br />