Laserfiche WebLink
<br />~ <br />Ie ~ <br />1 <br />] <br />] <br />] <br />] <br /> <br />] The boiler system provides hot water for heating throughout the facility. The boilers <br />and heating pumps serve all air handlers, variable air volume boxes, radiation, and cabinet <br />unit heaters. The correct operation of this unit is critical because a failure of these <br />1 components while no one is in the building could prove to be extremely detrimental. The <br />,J lead/lag operation of the heating system pumps is not operational and action should be taken <br />as soon as possible to correct this deficiency. <br /> <br />[1. This unit is not operating according to the original design specifications as described in <br />1Jl section 3.03 in control section 15950. Furthermore, the current operation of the unit does not <br />match the sequence of operation as described in the as built drawings delivered to the owner <br />from the controls contractor. <br />Please see this section for further infonnation on all observations. <br /> <br />D <br />o <br />o <br />o <br />o <br />o <br />[J <br />u. <br />u <br /> <br />Functional Test <br /> <br />Boilers 1 and 2 <br /> <br />Project: Arden Hills City Hall <br /> <br />Equipment Tag: B-1/B-2 <br /> <br />Party filling out this fonn & witnessing <br /> <br />Greo Zernechel <br /> <br />Date of test 30 Jan 03 <br />