Laserfiche WebLink
.ĻƌƌĻǝźƌƌĻ \[ğƓķźƓŭ ΛЊЉЌ ǒƓźƷΜʹ DƩƚǒƦ wЋ <br /> All areas will require a sprinkler system per NFPA 13R, MSFC 903.2.7 and <br />Chapter 1306 as adopted. <br /> Class I, Wet Standpipe required in each stairwell <br /> Hydrants required within 400 feet of all portions of the building with a <br />minimum flow of 500 gpm (exte <br /> aerial apparatus. Where there is a <br />hydrant on an access road the width will need <br /> All Fire lanes are required to be posted per MSFC sec. D103.6 <br /> Locked key box required for emergency access (location coordinated with <br />bldg. owner) <br /> Landscaping not to block/interfere with access to Fire Department <br />Connection <br /> <br />Additional required systems/features will be will be commented on or approved <br />as final plans are submitted for construction. <br /> <br />Kathy Peil, Asst. Chief <br />Centennial Fire District <br />651-792-7906 <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br />