T0: Planning Commission <br />FROP�: Fi re P1arsl�al �� <br />SUB.IECT: �roposed rearganization of Rosevi�1e tiobil I�ame Park, <br />2599 PJorth Lexington Avenue <br />Ai the re�uest of the Assistant City Engineer, I have reviewed �he pra�a�ed <br />pl ars for the above su�ject pari�, and the fo� lo►�i ng changes wi 11 L�e necessary <br />ta insure adequate fire protectian ti�rithin tne complex: <br />1. Ther� m�st be a loop 6 ir�ch un�erground system prav�ded for <br />fire figi�ting and domestic purposes. The system should extend <br />up the �orth roadti,�ay and loop back to the souti� road back to <br />Lexington Avenue. Eigi�t standard f�re hydranis must be pro- <br />vid�d along the roadway system, spaced a maximum of 350 feet <br />apart. <br />2. Provide a 4 incn dry �andergro�rzd fire main alang the south side <br />of th� sauth roadway with a fire department siamese connection <br />at the south side of the south driveway. 7his fire main is to <br />be connected to a dry de7uge syst�m to be installed around tne <br />new �iquified petro7e�am storage tank. This protection system <br />is necessary �o provide immediate 4�ater spray on the storage <br />tank in the event of a�ire, ihis is a relatively new require- <br />ment and was formu1ated after the Wesfi St. Paul disaster invvl�ing <br />L.P. Gas a�d the �ire Depar�ment's inal�iiity to apply water to the <br />iiquified pe��tro�eum storaqe tank. <br />3. The praposed three 1.,Op0 gailan L.P. gas tanlcs along the south side <br />of the proper~ty ar� not acceptable. These three tanks �rovide t�ree <br />times the exposure and hazard prablems that a si€�gTe tanEc wauid <br />present. In 7ieu �f the three separate storage tan[cs, we recommend <br />that one 15,000 g�ilon L.�. gas storage tank be insta�l�d �o pravide <br />ad��uate fuel fa�~ the heating syst�ms V�ithin the mabil homes. The <br />State a�d local fire codes req�ir� that the storage tandc have a s�t- <br />back minim�m of 5Q feet from any praperty lin� �,rhich m�y b� buiIt <br />upon and 50 feet �rom any building or group of build�ngs. ihe present <br />plans s�ow the L.n. Gas tanks approximately 10 ���t off from the rigt�t- <br />of-�ay on Rose Plac�. This location wilI be acc�ptable if Rose Place <br />is vacated and a r�strict7on be placed on the deed to prevent any <br />building within 5a teet of th� L.P, storage tanks. Ir� �ieu of this <br />it wi�l be necessary to install the L.P. gas storage tanlc 5Q feet <br />fro�m the north ri ghi-of-�ray 1 i ne �f Rose PI ace. <br />At the present time the fire protection fea�ures of this mobile home parfc are <br />nearly non-exis��nt. ihe amaur+t of hase that is required to be jaid in order <br />to fight a fire in an �dvanced state in �h� mobile home park is far in �xcess <br />of any recognized code. l�lany of the buiTd�ngs are close �ogether with <br />