Laserfiche WebLink
<br />general purpose industrial use. Fluorescent fixtures <br />of the proper type distribution shall be used. The <br />maintained lighting levels must be 30 foot candles. <br /> <br />9. All conduit entering the building which is provided by <br />the vendor shall be provided with sealing provisions <br />inside the building. Crouse-Hinds type EYS fittings <br />shall be used. <br /> <br />10. The main grounding loop shall be connected to the <br />building or enclosure by others. Grounding lugs shall <br />be provided, one at each end of the building or <br />enclosure, for purposes of grounding the building or <br />enclosure. Grounding lugs shall be suitable for <br />grounding with 250MCM copper wire minimum. <br /> <br />11. Each low voltage control enclosure shall contain one <br />120V duplex receptacle, 3 wire grounding type, 20A and <br />one overhead light receptacle and light switch. <br /> <br />12. Each cubicle compartment with an outside door shall be <br />provided with a thermostatically controlled, 120 volt, <br />300 watt (minimum) space heater. Expanded metal covers <br />shall be provided for each heater, unless such space <br />heaters already have a safety cover. Each cubicle shall <br />have its own thermostat. <br />