Laserfiche WebLink
<br />Air Emission Pennit No. 12300387-9 <br />Page 4 of22 <br /> <br />PART 1. EMISSION POINT SUMMARY <br /> <br />AQ Stack I.D. No.: <br /> <br />43 <br /> <br />Facility StackIV ent Designation: 43 <br /> <br />Unit Emission Unit Rated Install <br />No.: Manufacturer Model No.: Description: Capacity: Date: <br />48 Process to be Electroless Copper Plating 175 panels/hr 4/97 <br /> Automation determined Line Maximum <br /> Limited panel size: <br /> 21.5"x 27.5" <br /> <br /> Other <br /> Compliance Applicable <br /> Basis Demonstration Permit <br /> Requirement (If Applicable) (If Applicable) Parts <br />Emission Other Condition: <br />Limits: 1. PM: Not to exceed 1. Minn. R. Stack test as Part 4, <br /> 0.085 gr/dscf 7011.0715, requ~ed Part 6.2 <br /> 2. Opacity: Not to subp. LA. <br /> exceed 20% 2. Minn. R. <br /> 7011.0715, <br /> subp. I.B <br />Pollution Other Condition: Part 6.1. <br />Control Packed bed scrubber Minn. R, <br />Equipment 7007.0800, <br />Description subp.2 <br />Pollution Other Condition: Part 6.1. <br />Control flowmeter, pressure Minn. R. Part 3.1. <br />Equipment gauge 7007.0800, <br />Monitoring subp. 14 <br />Equipment <br />Pollution Other Condition: Part 6.1. <br />Control Water flow rate shall Minn. R. <br />Equipment be 40 to 70 gal.lmin. 7007.0800, <br />Operating and pressure drop subp. 14 <br />Parameter range shall be 0 to 3 <br />Limits inches of W.C. in order <br /> to ensure proper <br /> operation of the <br /> controlequipD1ent <br />