<br />3.0 RESULTS OF INSPECTION <br /> <br />3.1 Types of ACM Identified <br /> <br />Refer to the INSPECTION RESULTS TABLE for details of the <br />results. <br /> <br />Friable Thermal Insulation <br /> <br />The friable asbestos-containing material identified in the <br />NCR Comten Training Center is thermal systems insulation. <br />The water heater tank insulation and the pipe fittings <br />insulation were found to contain asbestos. A 6 inch pipe, <br />approximately 10 feet long, on the boiler is wra~ped with <br />asbestos-containing insulation. The remaining ~1pe <br />insulation in the building is not asbestos. (F1gure 1) <br /> <br />Nonfriable Floor Tile <br /> <br />The 9" x 9" floor tiles sampled in the training center <br />(Figure 3) were sampled and found to contain asbestos. The <br />floor tiles are a nonfriable material until they are broken <br />up. Isolated areas are damaged and the majority of the tile <br />are very brittle. The mastic was found not to contain <br />asbestos. <br /> <br />The 12" x 12" floor tiles are not asbestos. <br /> <br />Miscellaneous Materials <br /> <br />2' x 4' ceiling tiles were sampled in the Facility (Figure 2) <br />and are not asbestos. <br /> <br />The sheetrock panels and tectum ceiling were sampled and are <br />not asbestos. <br /> <br />3.2 Quantity Summary of ACM Identified <br />The approximate quantities of ACM identified are as follows: <br />- Thermal Systems Insulation = 120 Fittings <br />10 Linear Feet <br /> <br />- Thermal Water Heater Insulation = <br /> <br />210 Square Feet <br /> <br />- Floor Tile (9" x 9") <br /> <br />= 7,500 Square Feet <br /> <br />3.3 Analytical Results <br />Refer to the attached Braun Laboratory Report <br /> <br />lea COHTEN ASBESTOS REPORT <br /> <br />PAGE 3 <br />