Laserfiche WebLink
<br />CONTROL BUILDING SPECIFICATIONS. <br /> <br />34' X 12' X 14' Pre- Engineered Metal Building. <br /> <br />~ Base Frame. <br /> <br />Buildings shall be mounted on an I-beam and structural steel <br />channel frame. When completed, each entire assembly shall <br />be suitable for transportation as a single package. <br />Removable lifting lugs shall be provided, bolted to the base <br />frame, as a means to lift and set the building or enclosure. <br /> <br />~ Floor. <br /> <br />Floors shall be 3/16" steel plate (minimum). The finished <br />floor shall have no visible unevenness or warpage. Floor <br />insulation shall have an exterior sheet metal sheathing. <br /> <br />Floor areas designed for conduit entry shall remain <br />un-insulated with no metal sheathing. <br /> <br />~ Walls. <br /> <br />Double wall construction shall be used throughout, including <br />exterior switchgear access doors and floors. Exterior walls <br />shall be minimum 14 gauge, cold rolled steel. All insulation <br />shall be completely enclosed by metal. <br /> <br />~ Insulation. <br /> <br />Buildings and enclosures shall be completely insulated <br />including ceiling, walls and doors but excluding conduit <br />entry area with fiberglass or other Amoco approved <br />insulation. Insulation must have low water absorption and <br />low or zero fuel contribution. Minimum R values shall be: <br /> <br />Walls and Doors: R19 <br />Ceilings and Floors R38. <br /> <br />~ Roof Construction. <br /> <br />1. Roofs shall be built in such a manner as to be <br />completely water tight and shall be sloped to permit <br />water run off. <br /> <br />2. Roofs shall be built such that they may be walked upon <br />