Laserfiche WebLink
0 <br />approved by Landlord. Engineering and designs showing structural <br />loads added and all supports shall be furnished and installed by <br />Tenant. Routing of ductwork serving special exhaust and make-up air <br />systems shall be designated and/or approved by Landlord. Tenant's <br />ducts passing through the roof shall have motorized shut-off <br />damper(s). <br />F. Special cooling and heating equipment,, such as required for <br />refrigerated display cases, walk-in coolers, steam presses, etc., <br />shall be provides' by Tenant. <br />G. openings through roof. At Tenant's written request and for Tenant's <br />equipment, based upon approved plans, Landlord's roofing contractor <br />will, at Tenant's cost, provide the openings, anchoring devices, <br />curbs, fleshings, patching, etc., necessary to maintain the integrity <br />and guarantee of the roof. Minimum distance from roof edge is 10' <br />for all penetrations. <br />III. Tom' S PI24MM DESIGN CRITERIA <br />A. Tenant's sanitary, vent and domestic water piping shall adhere to <br />all local code requirements. <br />B. Water supplies to fixtures shall be valved at fixtures. <br />c. Domestic hot and -old wat-x piping shall be insulated. <br />D. Piping shall be supported from hangers at an adequate distance <br />with adequate supporting hanger rods fastened to bui]dinlj framing <br />whenever possible. <br />E. Watpr- heaters shall be equipped with UL approved temperature and <br />pressure relief valves. <br />F. Tenant water closets shall be flush tank type. <br />G. Hair Interceptors. Individual hair interceptors shall be installed <br />- 3 - <br />