Laserfiche WebLink
c. Sprinkler heads shall be indentical to those installed by <br />Landlord unless otherwise approved by Landlord in writing. <br />d. Tenant's sprinkler system shall be tested at water pressure <br />of 200 PGIG for a period to two (2) hours in the presence of <br />Landlord's representative. <br />e. Tenant's alterations to the system shall meet the requirements <br />of the City of Arden Hills, Minnesota, and the Insurance Services <br />Office of Minnesota. <br />f. Landlord's sprinkler system will become active on a schedule <br />established by Landlord. <br />Iv. �"TRIC DESIGN CRITERIA <br />A. TENANT'S WORK <br />Tenant shall design and install a complete electrical system within <br />the Premises including, but not limited to, the following items and <br />in accordance with the following criteria: <br />1. Transformers, conduits and branch wiring, outlet boxes, and <br />final conection to electrical devices including equipment. <br />2. Additional lighting fixtures and lamps, time clocks, clocks <br />and signs. <br />3. Telephone equipment, phone alert system, conduit and outlet <br />boxes. <br />4. Security equipment with conduit and outlets if desired. <br />5. Exit lights and emergency lighting as required by local codes <br />and ordinances. <br />6. All wiring shall be placed in conduit including telephone, <br />security alarm, music and control wiring. <br />0•10 <br />