Ordinance Title
An ordinance relating to the installation, alteration, repair or service to gas burners, gas burner equipment and to portable or domestic incinerators installed in connection with gas space heating devices and vented into the same chimney flu; estab
Ordinance Date Passed
8/18/1953
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
20
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
<br />1137 <br /> <br />The draft hood shall be placed in and made a part of the flue pipe from the <br />applicmce or shall be in the appliance itself, Such device shall have a free <br />area equal to or greater than the cross-sectional area of the flue pipe connected <br />thereto subject to the approval of the Gas Inspector. <br /> <br />SECTION 2 - 10.1 <br /> <br />The draft hood shall be located at a point not lower than the top of the <br />highest flue passage in the appliance. <br /> <br />SECTION 2 - 10.2 <br /> <br />Appliances of the revertible flue type shall have the draft hood located at <br />least one foot higher than the top of the highest fl~ passage. Proper provision <br />shall be made, subject to the approval of the Gas Inspector, to prevent the <br />accumulation of gas in any part thereof. <br /> <br />SECTION 2 - 11 FLUE PIPES: <br /> <br />The internal cross-sectional area of the flue pipe. between the appliance <br />and the chimney liner shall be such as to provide not less than one square inch <br />of flue area per 7,500 hourly BTU input. In no case- shall this flue pipe be <br />less than five (5) inches 1.n diameter for central heating gae appliances nor <br />less than foUr (4) inches in diameter for space heating appliances and it shall <br />not be larger than the next integral inch diameter above tbJ! size given in the <br />following table: <br /> <br />MINIMUM PERMISSIBLE FLUE SIZES <br />FOR GAS BURNER INSTALLATIONS <br /> <br />Input Rating <br />BTU per <br />Hour <br /> <br />..\rea of <br />Flue Outlet <br />Sq. In. <br /> <br />Diameter of <br />Flue Pipe . <br />Inches <br /> <br />94,500 12.6 4 <br />147,000 19.6 5 <br />212,250 28.3 6 <br />288.150 38.5 7 <br />311,250 50.3 8 <br />477,000 63.6. 9 <br />Based on 1 sq.in. flue area per 7,500 BTU per hour input. <br />Note: If flue pipe exceeds 10 feet in length or contains more than two <br />elbows, use next size larger pipe and draft hood. <br />In cases where the outlet from the appliance is larger than the above <br />indicated size, an orifice plate may be inserted, or a section of the flue pipe <br />restricted to the size indicated between the appliance outlet and the draft <br />diverter. <br />In special cases with high chimneys or flues the above schedule of areas <br />may be modified subject to specific approval of the Gas Inspector. <br />